Products
Contact Information
whatsapp:+8617775888159
E-mail:htcable@huataiglobal.com
Address: Xiadopu Machinery Industrial Park, Ningxiang, Xiangjiang New District, Hunan Province
Power Cable :
Fire resistant cable
Application scope:
fire resistant cable is suitable for high-rise buildings, entertainment places and many high-quality and highly safe building projects. It is used for power supply lines in fire elevator, fire pump, fire alarm, smoke exhaust system, emergency lighting, fire hazard area, high-temperature occasions and facilities requiring special safety in fire protection system
Product executive standard:
fire resistant power cable products shall comply with GB / T 12706-2020 and GB / T 19666-2019; Fire resistant control cables shall comply with GB / T 9330-2020 and GB / T 19666-2019
Product model and name
| Type | Name |
|
N-VV |
Rated voltage 0.6/1kv copper core PVC insulated PVC sheathed fire-resistant power cable |
|
N-YJV |
Rated voltage 0.6/1kv copper core XLPE insulated PVC sheathed fire-resistant power cable |
|
WDZN-YJY |
Rated voltage 0.6/1kv copper core cross-linked polyethylene insulated low smoke halogen-free polyethylene sheathed fire-resistant power cable |
|
N-VV22 |
Copper core PVC insulated PVC sheathed steel tape armored fire-resistant power cable with rated voltage of 0.6/1kv |
|
N-YJV22 |
Copper core XLPE insulated PVC sheathed steel tape armored fire-resistant power cable with rated voltage of 0.6/1kv |
|
WDZN-YJY23 |
Rated voltage 0.6/1kv copper core XLPE insulated low smoke halogen-free alkene sheathed steel tape armored fire-resistant power cable |
|
N-KVV |
Rated voltage 450 / 750V copper core PVC insulated PVC sheathed fire-resistant control cable |
|
N-KVVP |
Rated voltage 450 / 750V copper core PVC insulated PVC sheathed copper wire braided shielded fire-resistant control cable |
|
N-KVVP2 |
Rated voltage 450 / 750V copper core PVC insulated PVC sheathed copper tape wrapped shielded fire-resistant control cable |
|
N-KYJV |
Rated voltage 450 / 750V copper core cross-linked ethylene insulated PVC sheathed fire-resistant control cable |
|
N-KYJVP |
Rated voltage 450 / 750V copper core XLPE insulated PVC sheathed copper wire braided shielded fire-resistant control cable |
|
N-KYJVP2 |
Rated voltage 450 / 750V copper core XLPE insulated PVC sheathed copper tape wrapped shielded fire-resistant control cable |
|
WDZN-KYJY |
Rated voltage 450 / 750V copper core cross-linked ethylene insulated low smoke halogen-free flame retardant polyolefin sheathed fire-resistant control cable |
|
WDZN-KYJYP |
Rated voltage 450 / 750V copper core crosslinked ethylene insulated low smoke halogen-free flame retardant polyolefin sheathed copper wire braided shielded fire-resistant control cable |
|
WDZN-KYJY23 |
Rated voltage 450 / 750V copper core XLPE insulated low smoke halogen-free resistance alkene sheathed steel tape armored fire-resistant control cable |
Main technical parameters of the product
C rated voltage: U0 / u 0.6/1kv
Maximum long-term working temperature: PVC insulation 70 ℃, XLPE insulation 90 ℃
Minimum ambient temperature: flame retardant PVC sheath fixed laying - 40 ℃, non fixed laying - 15 ℃
Fire resistance characteristics:
| Comply with iec331 | Flame temperature 750 ℃, combustion time 3h, cooling time 12h, additional rated voltage, additional 3A current |
| Comply with GB/19666-2019 | Flame temperature 750-800 ℃, combustion time 90min, additional rated voltage 3A current |
Recommended allowable bending radius for laying: the non armored cable shall not be less than 20 times of the outer diameter of the cableArmored cable shall not be less than 12 times of cable outer diameter
| Type | Core | Nominal section mm2 |
50Hz Withstand voltage test |
Fire resistance characteristics |
|
N-YJVN-VV WDZN-YJY |
1 |
1.5~300 |
3.5KV/5min |
Pass GB/T19666-2019 Line integrity test |
WDZN-YJY63 |
10~300 |
|||
|
N-YJVN-VV WDZN-YJY |
2 |
1.5~185 |
||
|
N-YJV22N-VV22 WDZN-YJY23 |
4~185 |
|||
|
N-YJVN-VV WDZN-YJY |
3、4、5 |
1.5~300 |
||
|
N-YJV22N-VV22 WDZN-YJY23 |
2.5~300 |
|||
|
N-YJVN-VV WDZN-YJY |
3+1、3+2、4+1 |
2.5~300 |
||
|
N-YJV22N-VV22 WDZN-YJY23 |
4~300 |
|||
|
N-KVV N-KYJV N-KVVP N-KYJVP N-KVV22 N-KYJV22 WDZN-KYJYP |
2-61 |
0.5-10 |
3.0KV/5min |
Pass GB/T19666-2019 Line integrity test |
The outer diameter of fire-resistant cable with a section of 25mm2 or less is 15% larger than that of ordinary similar products, and the section of 25mm2 or more is 25% larger than that of ordinary similar products
The electrical and physical mechanical properties of the product are the same as those of ordinary products
The current carrying capacity of fire-resistant cables is the same as that of similar types of cables